Main
conductor cable and grounding rods
Conductor cable must
interconnect all air terminals (points) and shall form a two-way path
from each air terminal horizontally or downward to connection with
grounding rods.
Exceptions to the
above rule are:
- When the conductor
cable drops from a higher to lower level providing the lower roof
conductor horizontal run does not exceed 40 feet,
- Air terminals may
be dead ended with only one path to a main conductor on roofs below
the main protected roof provided the conductor maintains a
horizontal or downward run and is not more than 16 feet long.
Conductor cable shall
maintain a horizontal or downward course, free from any "V" or
"U" pockets, when a "V" or "U" pocket is
necessary, a down connector must be provided from the base of the pocket
to a convenient main conductor on a horizontal or downward path.
A conductor cable must
not be through the air unsupported for a distance of more than 3 feet.
Ridge conductors shall be coursed along ridges of gable, gamble and hip
roofs and around the perimeter of flat and gently sloping roofs.
Conductor cable must be coursed through or around obstructions such as
ventilators, chimneys, cupolas and the like. in a horiziontal plane with
the main conductor.
Down conductors shall
be as widely separated as possible and located at the perimeter of a
roof structure. Their location will depend upon location of air
terminals, the most direct coursing of cable, the location of utilities,
metallic piping and etc.
There shall be a
minimum of two down conductors on any kind of structure. Structures with
a perimeter exceeding 250 feet shall have a down conductor for every 100
feet of perimeter.
a main sized conductor
cable shall be used to interconnect electric service, antenna grounds,
metallic water piping, telephone systems and other large grounded
metallic masses.
Each down conductor
must terminate in a copper-clad ground rod or grounding plate. In sand
or gravel soil, at each grounding location, two or more ground terminals
at least 10 feet apart shall be driven vertically to a minimum depth of
10 feet, If bed rock is near the surface, copper conductor cable
shall be laid in a minimum trench length of 12 feet and 2 feet deep
extending away from the building at each down conductor.